HSRX

The HSRX Self-Regulating Heating Cable is designed for freeze protection and high process temperature maintenance of metal and non-metal pipes, vessels, and equipment where steam cleaning is required.

HSRX heating cable system is certified for ordinary and hazardous areas with maximum maintain temperature of 300°F (150°C) and intermittent exposure temperature of 482°F (250°C). Use of Indeeco connection kits for HSRX installation is required to comply with system approval, ensuring safe operation and reliable thermal performance.

 

 

Approvals

Product Inquiry

Specifications

Max. Intermittent Exposure Temp.

  • 482°F (250°C)

Max. Maintain or Continuous Exposure Temp.

  • 300°F (150°C)

Supply Voltage

  • 120V or 208 – 277V

Output Wattage

  • 5, 10, 15, 20W/ft @50°F (16, 33, 49, 66W/m @10°C)

Bus wire

  • 16 AWG

Min. Bending Radius

  • 0.8″ @70°F (20mm @20°C), 1.8″ @-76°F (45mm @-60°C)

Specifications

Min. Installation Temperature

  • -76°F (-60°C)

Min. Start-up Temperature

  • -40°F (-40°C)

Max. Circuit Breaker Size

  • 50A

Outer Jacket Color

  • Red

Heating Cable Dimensions (Nominal)

  • 0.50″ x 0.20″ (13.0mm x 5.0mm)

Heating Cable Weight

  • 0.0902lb/ft (0.134kg/m)

Closed Tank Heating

Watt Density

Percentage of Wattage

Need a quote?